Plan Review Notes
Plan Review Notes For Permit 12080136
Permit Number 12080136
Review Stop B
Sequence Number 2
Notes
Date Text
2012-08-08 16:09:15RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 07-1219.09 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3
 OF 2010 FBC-RESIDENTIAL.
  
 ***NOTE: ENGINEERING CALCULATIONS SUBMITTED ARE MISSING
 THE FOLLOWING:
  
 A) RAS 117 CALCULATIONS WERE NOT SUBMITTED.
  
 B) CALCULATIONS ARE MISSING THE BUILDING EXPOSURE.
 ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED
 ON EXPOSURE "C".
  
 C) CALCULATIONS SUBMITTED ARE FOR MONOSLOPE ROOF
 BETWEEN 10 AND 30 DEGREES. NEED CALCULATIONS FOR THE
 FLAT ROOF 0 TO 10 DEGREES.
  
 D) THE TRIBUTARY AREA FOR THE ROOF ZONES IS NOT 100
 S.F. SEE NOTE (A) OF TABLE R301.2(2) OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 E) SPECIFY THE MEAN ROOF HEIGHT.
  
 F) SPECIFY THE ULTIMATE AND NOMINAL WIND LOADS.
  
 G) ENGINEER TO PROVIDE ALL HIS INFORMATION AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712