Plan Review Notes For Permit 12080136 |
Permit Number |
12080136 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-08-08 16:09:15 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | 07-1219.09 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO | | MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3 | | OF 2010 FBC-RESIDENTIAL. | | | | ***NOTE: ENGINEERING CALCULATIONS SUBMITTED ARE MISSING | | THE FOLLOWING: | | | | A) RAS 117 CALCULATIONS WERE NOT SUBMITTED. | | | | B) CALCULATIONS ARE MISSING THE BUILDING EXPOSURE. | | ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED | | ON EXPOSURE "C". | | | | C) CALCULATIONS SUBMITTED ARE FOR MONOSLOPE ROOF | | BETWEEN 10 AND 30 DEGREES. NEED CALCULATIONS FOR THE | | FLAT ROOF 0 TO 10 DEGREES. | | | | D) THE TRIBUTARY AREA FOR THE ROOF ZONES IS NOT 100 | | S.F. SEE NOTE (A) OF TABLE R301.2(2) OF 2010 | | FBC-RESIDENTIAL. REVISE AS REQUIRED. | | | | E) SPECIFY THE MEAN ROOF HEIGHT. | | | | F) SPECIFY THE ULTIMATE AND NOMINAL WIND LOADS. | | | | G) ENGINEER TO PROVIDE ALL HIS INFORMATION AS REQUIRED | | BY CHAPTER 471 FLORIDA STATUTE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|