Plan Review Notes For Permit 12080123 |
Permit Number |
12080123 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-08-06 11:24:36 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- SELECTED FLAT ROOF SYSTEM W-14 FROM FLORIDA PRODUCT | | APPROVAL SUBMITTED DOESN'T MEET THE DESIGN PRESSURES | | REQUIRED BY SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY NOTE #8 ON FLORIDA PRODUCT APPROVAL | | FL10497-R1 SUBMITTED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|