Plan Review Notes For Permit 12080080 |
Permit Number |
12080080 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2012-11-06 10:24:39 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1- PROVIDE ENERGY CALCULATIONS. | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FRENCH | | DOORS. NOA 08-0821.09 SUBMITTED WAS SUPERSEDED. | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE DOORS | | PRODUCT APPROVAL. | | 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE | | INSTALLATION OF THE ALUMINUM BAHAMA SHUTTERS. | | 5- NEW SECTION B-B ON SHEET A-2: | | A) SPECIFY INSULATION ON THE DEMISING WALL BETWEEN THE | | GARAGE AND THE OFFICE. SEE ENERGY CALCULATIONS. | | B) PROVIDE COMPLETE SPECIFICATIONS FOR THE 1 HR | | DEMISING WALL BETWEEN THE GARAGE AND THE OFFICE. WHERE | | IS THE GA FILE NO WP1072?. |
|