2012-11-05 08:39:24 | BUILDING REVIEW SECOND CHECKLIST: | | CODE:2010 FBC. | | | | | | 1- PROVIDE ENERGY CALCULATIONS. SEC.103.2 OF 2010 | | FBC-ENERGY CONSERVATION. | | ***NOTE: THIS IS NOT A CONTRIBUTING HISTORIC BUILDING, | | THEREFORE, HISTORIC EXEMPTION DOESN'T APPLY. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FRENCH | | DOORS. NOA 08-0821.09 SUBMITTED WAS SUPERSEDED BY | | MIAMI-DADE. REQ'D DCA RULE 9N-3. (REPEAT COMMENT). | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE DOORS | | PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS TO | | FBC. | | | | 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE | | INSTALLATION OF THE ALUMINUM BAHAMA SHUTTERS. SEC. | | 107.2.1 CITY AMENDMENTS TO FBC. (REPEAT COMMENT). | | | | 5- NEW SECTION B-B ON SHEET A-2: | | A) SPECIFY INSULATION ON THE DEMISING WALL BETWEEN THE | | GARAGE AND THE OFFICE. COORDINATE WITH THE ENERGY | | CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY | | CONSERVATION. | | | | B) PROVIDE COMPLETE SPECIFICATIONS FOR THE 1 HR | | DEMISING WALL BETWEEN THE GARAGE AND THE OFFICE. WHERE | | IS THE GA FILE NO WP1072?. SEC. 107.2.1 CITY AMENDMENTS | | TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|