2012-08-29 14:39:19 | BUILDING PLAN REVIEW |
| PERMIT: 12080060 |
| ADD: 4705 BROADWAY |
| CONT: CILAS CONCRETE |
| TEL: (561)255-3725 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW 8/29/2012 |
| ACTION: DENIED |
| |
| 1) 2010 FBC-B 439.2 WALLS SEPARATING DWELLING UNITS IN |
| THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS IN |
| THE SAME BUILDING AND WALLS SEPARATING DWELLING OR |
| SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE |
| PARTITIONS IN ACCORDANCE WITH SECTION 709. |
| |
| 2) 2010 FBC-B TABLE 508.4 REQUIRED SEPERATION OF |
| OCCUPANCIES BETWEEN RESIDENTIAL OCCUPANCIES AND STORAGE |
| OCCUPANCIES REQUIRES 2 HOUR FOR NON-SPRINKLERED |
| BUILDINGS. |
| |
| 3)THE WALL IS NOT INDICATED TO CONTINUE TO THE DECK |
| ABOVE, PROVIDE A ASSEMBLY WITH A 2HOUR RATING. |
| 709.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE |
| TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW |
| TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB |
| OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED |
| FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL |
| BE SECURELY ATTACHED THERETO. IF THE PARTITIONS ARE NOT |
| CONTINUOUS TO THE SHEATHING, DECK OR SLAB, AND WHERE |
| CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION, THE SPACE |
| BETWEEN THE CEILING AND THE SHEATHING, DECK OR SLAB |
| ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN |
| ACCORDANCE WITH SECTIONS 717.2 AND 717.3 AT THE |
| PARTITION LINE. THE SUPPORTING CONSTRUCTION SHALL BE |
| PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING |
| OF THE WALL SUPPORTED, EXCEPT FOR WALLS SEPARATING |
| TENANT SPACES IN COVERED MALL BUILDINGS, WALLS |
| SEPARATING DWELLING UNITS, WALLS SEPARATING SLEEPING |
| UNITS AND CORRIDOR WALLS, IN BUILDINGS OF TYPE IIB, |
| IIIB AND VB CONSTRUCTION. |
| |
| 4) 709.4.1 ROOF CONSTRUCTION. WHEN THE FIRE PARTITION |
| IS CONTINUOUS TO THE UNDERSIDE OF THE ROOF SHEATHING IN |
| OCCUPANCIES OF GROUPS R-1, R-2 AND R-3 AS APPLICABLE IN |
| SECTION 101.2, IN TYPE III, IV AND V CONSTRUCTION THE |
| FOLLOWING SHALL BE PROVIDED: |
| 709.4.1.1 ROOF SHEATHING. |
| |
| THE ROOF SHEATHING OR DECK SHALL BE OF APPROVED |
| NONCOMBUSTIBLE MATERIALS OR OF FIRE-RETARDANT-TREATED |
| WOOD, FOR A DISTANCE OF 4 FEET (1220 MM); OR |
| 709.4.1.2 ROOF PROTECTION. |
| |
| COMPLIED: THE ROOF SHALL BE PROTECTED WITH 0.625-INCH |
| (15.88 MM) TYPE X GYPSUM BOARD DIRECTLY BENEATH THE |
| UNDERSIDE OF THE ROOF SHEATHING OR DECK, SUPPORTED BY A |
| MINIMUM OF NOMINAL 2-INCH (51 MM) LEDGERS ATTACHED TO |
| THE SIDES OF THE ROOF FRAMING MEMBERS, FOR A MINIMUM |
| DISTANCE OF 4 FEET (1220 MM). |
| |
| 5) COMPLIED. |
| |