Notes |
Date |
Text |
2012-08-04 21:38:57 | 4705 BROADWAY | | PERMIT #12080060 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SECTION A-1 INDICATES ONLY ONE 5/8" LAYER OF FIRE RATED | | GYPSUM BOARD. INDICATE HOW THIS EQUATES TO A 2-HOUR | | FIRE SEPARATION. | | | | SUBMIT PRODUCT DATA FOR FIRE CAULK. | | | | NOTE: THERE IS EXISTING ELECTRICAL CONDUIT RUNNING | | NORTH/SOUTH ALONG THE 2X8 WOOD JOISTS IN THE STORAGE | | ROOM. THIS WORK APPEARS TO BE UNPERMITTED AND WILL NEED | | TO BE INSPECTED BY THE ELECTRICAL INSPECTOR (PHIL | | PETTY) BEFORE ANY CEILINGS ARE TO BE INSTALLED. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|