Plan Review Notes
Plan Review Notes For Permit 12071100
Permit Number 12071100
Review Stop B
Sequence Number 1
Notes
Date Text
2012-08-02 11:05:18RESIDENTIAL (R1) RE-ROOF AND REPAIRS BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- A) ENGINEER TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR NEW BEAMS AND COLUMNS. NEED TO
 SPECIFY ALL BEAM STRUCTURAL CONNECTORS AND COLUMNS
 CONNECTORS AT TOP AND BOTTOM AS REQUIRED BY SEC.
 1604.8.1 OF 2010 FBC-BUILDING.
  
 B) ENGINEER TO REVISE APPLICABLE CODE SPECIFIED ON
 SHEET A-1. THE APPLICABLE CODE IS THE FBC-2010 NOT THE
 FLORIDA RESIDENTIAL CODE. SEC. 101.2 CITY AMENDMENTS TO
 FBC.
  
 C) SPECIFY THE ROOF PITCH AS REQUIRED BY SEC. 107.2.1.2
 CITY AMENDMENTS TO FBC.
  
 2- A) SPECIFY HOW IS THE CONCRETE TILE GOING TO BE
 INSTALLED. SPECIFY IF SCREWS (HOW MANY AND SIZE) OR
 ADHESIVE. IF USING ADHESIVE, THEN, SEE THE CONCRETE
 TILE NOA FOR LISTED ADHESIVE. AND, PROVIDE PRODUCT
 APPROVAL (2 COPIES) AS REQUIRED BY DCA RULE 9N-3 AND
 SEC. 107.2.1.2 OF CITY AMENDMENTS TO FBC.
  
 B) ENGINEER PLANS SPECIFY PEEL AND STICK CONCRETE TILE
 UNDERLAYMENT. PROVIDE PRODUCT APPROVAL DESIGNED FOR
 CONCRETE TILE INSTALLATION AS REQUIRED BY DCA RULE 9N-3
 AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. REVISE AS REQUIRED TO INCLUDE RE-ROOFING AND
 INSTALLATION OF NEW BEAMS AND COLUMNS AS SHOWN ON
 PLANS. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 ENGINEERING FEES AND OVERHEAD AND PROFIT AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6712
 [email protected].