2012-08-13 11:39:54BUILDING PLAN REVIEW
 PERMIT: 12071067
 ADD: 1950 N CONGRESS # 409
 CONT: CILAS CONCRETE
 TEL: (561)255-3725
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) DISCREPANCIES SHEET A-1 WIND INFORMATION IS
 INDICATED TO BE DESIGNED TO THE 2010 FBC-B BUT THE
 BASIC WIND SPEED IS INDICATED AS 140 MPH, 3 SECOND
 GUST.
 PLEASE SEE 2010 FBC-B FIGURE 1609A FOR CATEGORY LL
 BUILDINGS.
  
 2) DISCREPANCIES SHEET A-1 WIND INFORMATION IS
 INDICATING THIS BUILDING AS A SINGLE FAMILY HOME, IT
 APPEARS THE UNIT NUMBER BEING 409 THIS IS A R-2
 RESIDENCE LOCATED ON THE 4TH FLOOR. ADDITIONAL
 INFORMATION REQUIRED. 107.2.13 ALSO IF THIS UNIT IS
 LOCATED ON THE FOURTH FLOOR THERE SHOULD BE A
 ADJUSTMENT FACTOR FOR HEIGTH. A HEIGHT AND EXPOSURE
 ADJUSTMENT COEFFICIENT, * SHALL BE DETERMINED FROM 2010
 FBC-B TABLE 1609.7.2. ASCE 7-10.
  
 3) DISCREPANCY SHEET A-1 WINDOW TABLE OF POSTIVE &
 NEGATIVE WINDOW PRESURES IS FOR LAWSON WINDOWS WHEREAS
 PRODUCT APPROVALS SUBMITTED ARE PGT. PRODUCT APPROVALS
 SUBMITTED NOT PER PLAN. DISCREPANCY. 107.2.1.3.
  
 3) SHEET A-2 PRESSURES FOR SHEET A-2 ARE INDICATED AS
 FOR A BUILDING WITH A MEAN ROOF HEIGTH OF 15 FT. , IT
 IS NOT CERTAIN WITH THE LISTED ABOVE DISCREPANCIES IF
 THESE PRESSURES ARE V(ULT) OR V(ASD) SEE 2010 FBC-B
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved