2012-08-09 14:26:49 | PLANS DENIED | | 1) PROVIDE ENGINEER DETAILS ON THE PLANS FOR | | CURB TO ROOF TIE DOWN AND UNIT TO CURB TIE DOWN | | PER SECTION 301.12 WIND RESISTANCE. 2010 FBC (M) | | 2) REFER TO SECTION 606.2.1 SUPPLY AIR AND SECTION | | 606.4.1 SUPERVISION 2010 FBC (M) | | 3) CAN NOT LOCATE EXHAUST FANS 1,2,3 ON THE PLANS. | | 4) PROVIDE SEPARATE APPLICATION AND PLANS FOR HOODS | | AND WALK IN COOLERS . | | 5) REFER TO SECTION 506.3.10 DUCT ENCLOSES | | 2010 FBC (M) THE DUCT ENCLOSE SHALL SERVE A | | SINGAL GREASE DUCT AND SHALL NOT CONTAIN OTHER | | DUCTS PIPING OR WIREING SYSTEMS. | | 6) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | FOR FRESH AIR. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|