2012-08-09 14:26:49PLANS DENIED
 1) PROVIDE ENGINEER DETAILS ON THE PLANS FOR
 CURB TO ROOF TIE DOWN AND UNIT TO CURB TIE DOWN
 PER SECTION 301.12 WIND RESISTANCE. 2010 FBC (M)
 2) REFER TO SECTION 606.2.1 SUPPLY AIR AND SECTION
 606.4.1 SUPERVISION 2010 FBC (M)
 3) CAN NOT LOCATE EXHAUST FANS 1,2,3 ON THE PLANS.
 4) PROVIDE SEPARATE APPLICATION AND PLANS FOR HOODS
 AND WALK IN COOLERS .
 5) REFER TO SECTION 506.3.10 DUCT ENCLOSES
 2010 FBC (M) THE DUCT ENCLOSE SHALL SERVE A
 SINGAL GREASE DUCT AND SHALL NOT CONTAIN OTHER
 DUCTS PIPING OR WIREING SYSTEMS.
 6) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 FOR FRESH AIR.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]