2012-07-30 14:51:51 | 550 SOUTH ROSEMARY AVENUE - SUITE #148 |
| PERMIT #12070945 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| ****PROVISO**** SUBMIT REVISION |
| |
| UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS |
| PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL |
| BE PROVIDED. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| 500 NORTH DIXIE HIGHWAY. |
| |
| EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| FEET ON CENTER. |
| |
| PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| |
| SHEET A2.3: INDICATE THE SMOKE AND FLAME SPREAD RATING |
| OF THE CEILING DRAPERY. |
| |
| SHEET A-11.0: DOOR #101 - FOR ASSEMBLY OCCUPANCIES WITH |
| AN OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE |
| SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. |
| NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT |
| BE RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| PANIC HARDWARE, THE MAIN ENTRANCE (AND ONLY THE MAIN |
| ENTRANCE) IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR |
| LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING |
| "THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS |
| OCCUPIED." SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| HEIGHT. NOTE: A THUMB TURN STYLE LOCK IS NOT PERMITTED |
| TO BE SUBSTITUTED FOR A KEYED LOCK. |
| |
| SHEET A-11.0: DOOR #103A - NO OTHER LOCKS OR LATCHES |
| ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| HARDWARE. |
| |