 PLEASE ADD THE FOLLOWING INFORMATION TO THE ELECTRICAL
 PLANS:
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT. NEC 110.22, 110.16
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 PROVIDE THE MANUFACTURER?S SPECIFICATIONS AND LISTING
 ON THE 600 AMPERE ELECTRICAL SWITCHBOARD. VERIFY THE
 ELECTRICAL SERVICE DISCONNECT IS SERVICE RATED. NEC
 90.7, 230.79
 VERIFY THE OUTDOOR CEILING FANS AND LIGHT FIXTURES ARE
 RATED FOR DAMP LOCATIONS. NEC 90.7
 PROVIDE AN ELECTRICAL SYSTEM GROUNDING AND BONDING
 DIAGRAM. NEC 215.5, 250.24
  