2012-07-25 17:03:10RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- FLAT ROOF:
 A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY LIMITATION 5.6 OF FLORIDA PRODUCT APPROVAL
 FL2533-R7 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED IN
 EXPOSURE "D".
  
  
 B) PROVIDE THE FLORIDA PRODUCT APPROVAL COVER PAGE FOR
 PRODUCT APPROVAL FL2533-R7. SEC. 107.2 CITY AMENDMENTS
 TO FBC AND CITY POLICY FOR ROOFING PERMITS.
  
 2- TILE UNDERLAYMENT:
 A) FLORIDA PRODUCT APPROVAL FL11288-R7 SUBMITTED
 REQUIRES TO USE POLYFOAM POLYPRO AH160. SEE LIMITATION
 5.4.1. PROVIDE PRODUCT APPROVAL (2 COPIES) FOR AH160
 FOAM AS REQUIRED BY DCA RULE 9N-3.
  
 B) PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE FOR TILE
 UNDERLAYMENT FL11288-R7. SEC. 107.2 CITY AMENDMENTS TO
 FBC AND CITY POLICY FOR ROOFING PERMITS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER