Plan Review Notes
Plan Review Notes For Permit 12070928
Permit Number 12070928
Review Stop P
Sequence Number 1
Notes
Date Text
2012-07-27 08:37:152010 FBC
  
 DENIED BY PLUMBING
  
 1) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECTION 403.9.4 (3) AND HOUSE BILL 849 WHICH REQUIRE
 FILTRATION POOL PUMPS 1 HP AND GREATER TO HAVE A
 DEFAULT CIRCULATION SPEED THAT RESULTS IN A FLOW RATE
 THAT WILL NOT TURN THE POOL OVER IN LESS THAN SIX HOURS
 OR 36 GPM WHICHEVER IS GREATER WITH A HIGHER SPEED
 OVERRIDE CAPABILITY FOR A TEMPORARY PERIOD NOT TO
 EXCEED ONE NORMAL CYCLE OR 24 HOURS, WHICHEVER IS LESS.
 THE PLANS SPECIFY A 3.68 HR TURNOVER RATE AT 60 GPM.
  
 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS WITH PUMP
 CURVES FOR THE SPA AND POOL FILTRATION PUMP. THE
 MAXIMUM FLOW RATES FOR TWO SPEED OR VARIABLE SPEED
 PUMPS ARE REQUIRED TO BE USED TO DETERMINE THE WATER
 VELOCITY IN THE POOL PIPING. BASED ON THE INFORMATION
 ON PENTAIR'S WEBSITE, THE MAXIMUM FLOW RATE FOR THE 3
 HP PENTAIR VS-3050 IS 145 GPM AT 56 FT TDH. AT THIS
 RATE THE WATER VELOCITY IN THE 3" BRANCH PIPING IS 6.58
 FT/SEC WHICH EXCEEDS THE 6 FT/SEC WHEN ONE OF THE PAIR
 IS BLOCKED THAT IS ALLOWED BY ANSI / APSP- 7 2006
 SECTION 4.4. THE MAXIMUM FLOW RATE FOR THE 2 HP PENTAIR
 WHISPERFLO IS 140 GPM AT 39 FT TDH, WHICH RELATES TO A
 WATER VELOCITY OF 6.36 FT/SEC IN THE 3" PIPE. THIS
 EXCEEDS THE 6 FT/SEC ALLOWED IN THE BRANCH PIPING.
 PLEASE CORRECT. NOTE: ONLY THE BRANCH PIPING AT THE
 MAIN DRAINS DOES NOT COMPLY, THE REST OF THE SUCTION
 PIPING WILL COMPLY. IF CHANNEL DRAINS ARE USED IN LIEU
 OF THE TWO MAIN DRAINS, THERE IS NO BRANCH PIPING
 REQUIREMENT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]