Plan Review Notes For Permit 12070923 |
Permit Number |
12070923 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-09-08 16:45:59 | 700 SOUTH ROSEMARY AVENUE - SUITE #208 | | PERMIT #12070923 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - SUBMIT REVISION***** | | | | REMOVE THE EXIT SIGN ABOVE THE DOOR LEADING TO THE | | OUTSIDE DINING AREA OR REMOVE THE VERTICAL SECURITY | | GRILL. | | | | THE FIRE ALARM SYSTEM WILL NEED TO BE PROVIDED WITH | | VOICE EVACUATION WHEN THE OCCUPANT LOAD EXCEEDS 300 | | PERSONS IN AN EXISTING ASSEMBLY OCCUPANCY (REFERENCE | | SECTION 13.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE - | | NFPA 101). PROVIDE SPEAKER/STROBE NOTIFICATION | | APPLIANCES. PROVIDE A PRE-RECORDED FIRE ALARM | | EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS | | BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, | | AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE | | ELEVATOR. | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE WET CHEMICAL | | SUPPRESSION SYSTEMS, FIRE SPRINKLER SYSTEM AND FIRE | | ALARM SYSTEM. | | | | PLEASE INDICATE THE CODE REFERENCE EXCEPTION THAT | | PERMITS THE OMISSION OF A TYPE 1 EXHAUST HOOD OVER | | APPLIANCES PRODUCING GREASE-LADEN VAPORS OR SMOKE. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|