2012-09-08 16:45:59700 SOUTH ROSEMARY AVENUE - SUITE #208
 PERMIT #12070923
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 REMOVE THE EXIT SIGN ABOVE THE DOOR LEADING TO THE
 OUTSIDE DINING AREA OR REMOVE THE VERTICAL SECURITY
 GRILL.
  
 THE FIRE ALARM SYSTEM WILL NEED TO BE PROVIDED WITH
 VOICE EVACUATION WHEN THE OCCUPANT LOAD EXCEEDS 300
 PERSONS IN AN EXISTING ASSEMBLY OCCUPANCY (REFERENCE
 SECTION 13.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE -
 NFPA 101). PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES. PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE
 ELEVATOR.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE WET CHEMICAL
 SUPPRESSION SYSTEMS, FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 PLEASE INDICATE THE CODE REFERENCE EXCEPTION THAT
 PERMITS THE OMISSION OF A TYPE 1 EXHAUST HOOD OVER
 APPLIANCES PRODUCING GREASE-LADEN VAPORS OR SMOKE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  