2012-08-28 13:41:16PLANS DENIED
 1) PROVIDE HANGING DETAIL FROM THE ENGINEER FOR AIR
 HANDLERS
 SECTION 107 FBC 2010
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 FLORIDA ENERGY CODE.
 3) SEPARATE APPLICATION ,PLANS AND PERMITS REQUIRED FOR
 HOOD, COOLERS, FIRE SUPPRESSION AND HABACHI TABLES AND
 DUCT
 PER SECTION 107 FBC 2010
 4) PROVIDE EQUIPMENT SCHEDULE FOR NEW EXHAUST FANS AND
 NEW AIR HANDLERS PER SECTION 127 FBC 2010
 5) PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO
 ROOF TIEDOWN
 AND THE EXHAUST FAN TO CURB TIEDOWN PER SECTION 301.12
 WIND RESISTANCE FBC (M) 2010