Plan Review Notes For Permit 12070923 |
Permit Number |
12070923 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-08-28 13:41:16 | PLANS DENIED | | 1) PROVIDE HANGING DETAIL FROM THE ENGINEER FOR AIR | | HANDLERS | | SECTION 107 FBC 2010 | | 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | FLORIDA ENERGY CODE. | | 3) SEPARATE APPLICATION ,PLANS AND PERMITS REQUIRED FOR | | HOOD, COOLERS, FIRE SUPPRESSION AND HABACHI TABLES AND | | DUCT | | PER SECTION 107 FBC 2010 | | 4) PROVIDE EQUIPMENT SCHEDULE FOR NEW EXHAUST FANS AND | | NEW AIR HANDLERS PER SECTION 127 FBC 2010 | | 5) PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO | | ROOF TIEDOWN | | AND THE EXHAUST FAN TO CURB TIEDOWN PER SECTION 301.12 | | WIND RESISTANCE FBC (M) 2010 | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|