Plan Review Notes For Permit 12070794 |
Permit Number |
12070794 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-08-07 14:34:59 | PLANS DENIED | | 1) PROVIDE CALCULATIONS OF HEATING AND COOLING LOADS | | PER SECTION 503.2.1 2010 FLORIDA ENERGY CODE. | | 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | (FOR FRESH AIR) 2010 FLORIDA ENERGY CODE. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|