Plan Review Notes
Plan Review Notes For Permit 12070734
Permit Number 12070734
Review Stop E
Sequence Number 1
Notes
Date Text
2012-08-03 14:50:2212070734
 2301 OKEECHOBEE BLVD
 SITE LIGHTING
  
 PLEASE HAVE THE ENGINEER CLARIFY THE FOLLOWING:
  
 THE SITE PLAN SHOWS THREE POLE TYPES. THE POLE
 SPECIFICATIONS (TWO TYPES) DO NOT SEEM TO MATCH THE
 FIXTURE OR POLE CONFIGURATIONS SUBMITTED.
  
 THE WIND LOAD EFFECTIVE PROJECTED AREA (EPA) FOR THE
 POLES DOES NOT INCLUDE OR REFERENCE THE EPA FOR THE
 FIXTURES AND FLOOD LIGHTS. PLEASE IDENTIFY THE POLE
 TYPE SUITABLE FOR EACH FIXTURE.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER