Plan Review Notes
Plan Review Notes For Permit 12070677
Permit Number 12070677
Review Stop B
Sequence Number 1
Notes
Date Text
2012-07-19 14:40:53RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER TO PROVIDE ACTUAL RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 2- ENGINEER TO REVISE NAILING SPACING:
 A) THE MINIMUM FASTENER SPACING SHALL NOT BE LESS THAN
 4" O.C. SEE RAS 117 SEC. 8.1 AND REVISE AS REQUIRED.
  
 B) ALL FRACTIONS SHALL BE ROUNDED DOWN TO THE NEXT
 WHOLE NUMBER. SEE RAS 117 SEC. 10.4.5 AND REVISE AS
 REQUIRED.
  
 C) ENGINEER TO SPECIFY THE NAIL SPACING AT THE BASE
 SHEET LAP. MISSING THE INFORMATION. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL