2013-02-25 11:36:54 | | | 12070649 | | 501 FERN ST # C1 | | NEW FOOD MARKET | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH | | PROTECTION, HIGH-LEG MARKING, PANELBOARDS AND THE MAIN | | DISCONNECTING MEANS. REVISE PLANS TO SHOW THE SERVICE | | VOLTAGE BEING PROVIDED BY THE UTILITY. NEC 110.22, | | 110.16, 110.22 | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | RECEPTACLES ON ROOF REQUIRE GFCI PROTECTION. NEC | | 210.8(B) | | | | RISER PLAN APPEARS TO BE MISSING PANEL SLP? NEC 215.5 | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA, | | CABLE TV, POS, AND FIRE ALARM SYSTEMS. | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|