2013-02-15 10:54:48 | BUILDING PLAN REVIEW |
| PERMIT: 12070649 |
| ADD: 501 FERN ST |
| CONT: AUTO BUILDERS |
| TEL: (561)722-3956 |
| |
| 2007 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| FEB. 15/ 2013 |
| ACTION: DENIED |
| |
| 1) ADDITIONAL INFORMATION IS REQUIRED. THE SCOPE OF THE |
| PERMIT APPEARS TO HAVE CHANGED, THE PERMIT APPLICATION |
| UNDER THE DESCRIPTION OFPROJECT, DEMOLITION, STRUCTURAL |
| STEEL WORK SHELL ONLY. THE PLANS NOW HAVE A PLUMBING, |
| ELECTRICAL & MECHANICAL SHEETS, NEW DETAILS FOR A |
| MEZZANINE LEVEL. THE CONTRACTOR TO UPDATE THE SCOPE OF |
| WORK NO LONGER A SHELL, INCREASE THE VALUE OF THE |
| PERMIT, AND IS THIS A CHANGE IN OCCUPANCY, PROVIDE THE |
| TRYPE OF SERVICES WILL TAKE PLACE IN THIS BUILDING. |
| 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2) PROVIDE A KEY PLAN AS TO WHERE THIS SPACE IS LOCATED |
| WITHIN THE LAYOUT OF THE BUILDING, PROVIDE THE TYPE OF |
| OCCUPANCY WILL OCCUPY THIS TENANT SPACE. PROVIDE THE |
| MINIMUM BUILDING TYPE PER 2010 FBC-B TABLE 503. IS THIS |
| STRUCTURE FIRE SPRINKLERED OR NOT, IF SPRINKLERED A |
| LAYOUT OF SPRINKLERS OCCUPANCY TYPE AND OCCUPANT LOAD, |
| LIFE SAFETY PLANS WITH EGRESS, 107.3.5.1 MINIMUM PLAN |
| REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. |
| |
| 3) DISCREPANCY, THERE ARE TWO SETS OF STRUCTURAL SHEETS |
| WITH TWO COMPLETELY DIFFERNT SCOPE OF WORK EACH HAVING |
| A S1 & S2 SHEET NAME? THE CONTRACTOR OF RECORD WILL |
| NEED TO REVIEW DOCUMENTS TO SEE IF THE SCOPE HAS |
| CHANGED OR IF THE SHEETS SHOULD BE NUMERED S3 & S4? |
| COALATE PLANS. WHEN RESUBMITTING PLANS PLEASE INSERT |
| THE NEW SHEETS & REMOVE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 4) SHEET S-1 DATED JULY 17. 2012 INDICATES WIND DESIGN |
| PRESSURES WITH A "B" EXPOSURE, SHOULD BE A "C" WITH |
| PRESSURES BUT TO DATE NO PRODUCT APPROVAL WERE |
| SUBMITTED FOR: |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6) SINCE THERE ARE NO ARCHITECTURAL SHEETS IT IS NOT |
| CLEAR WHAT IS NEW AND WHAT IS EXISTING, PLEASE TO AWARE |
| OF 2010 ACCESSIBILITY CODE AND DISPROPORTIONATE COST. |
| |
| 202.4.1 DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 7)) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| |
| 8) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| A MEETING WITH THE CONTRACTOR BEFORE THE PLANS ARE |
| RESUBMITTED SHOULD BE ARRANGED TO BE ABLE TO REVIEW THE |
| PLANS, TO DATE IT IS NOT CLEAR THE INTENT OF THIS |
| PERMIT SINCE THE SCOPE OF THE PERMIT SEEMS TO HAVE |
| CHANGED!!!!!!!!!!!!!!!!! |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |