Plan Review Notes
Plan Review Notes For Permit 12070468
Permit Number 12070468
Review Stop B
Sequence Number 1
Notes
Date Text
2012-07-17 10:04:30RESIDENTIAL (R3) FLAT ROOF RE-ROOF BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA 12-0227.18 SUBMITTED.
 NEED THE CALCULATIONS TO MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 ***NOTE: WHEN DOING THE CALCULATIONS TAKE INTO
 CONSIDERATION THAT THIS BUILDING IS LOCATED ON EXPOSURE
 "D". SEE SEC. R301.2.1.4.3.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. THE PERMIT FEE
 BALANCE IS $159.52.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
 [email protected]