Plan Review Notes
Plan Review Notes For Permit 12070450
Permit Number 12070450
Review Stop B
Sequence Number 1
Notes
Date Text
2012-09-04 15:55:31PER S HILL OK TO CHG REVIEW STOP TO "N" AS SHE WILL BE
 TALKING TO K CONRAD REGARDING THIS REISSUE.
2012-08-15 13:44:54****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 SEE FBC RESIDENTIAL 301.1, RESISTANCE TO WIND LOADS:
  
 1. PLEASE INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED.
  
 2. CALCULATIONS PREPARED BY AN ARCHITECT, ENGINEER, OR
 REGISTERED ROOF CONSULTANT REQUIRED IF ENHANCED
 FASTENING IS REQUIRED, SEE GENERAL LIMITATION #7 ON THE
 LAST PAGE OF THE NOA.
  
 3. A CONTRACTOR LICENSED UNDER FS 489 FOR ROOF WORK, OR
 AN INDIVIDUAL WHO QUALIFIES UNDER ONE OF THE
 EXCEPTIONS, IS REQUIRED.
  