Plan Review Notes
Plan Review Notes For Permit 12070429
Permit Number 12070429
Review Stop E
Sequence Number 1
Notes
Date Text
2012-07-20 09:17:4512070429
 240 PALMETTO LANE
 20 KW GENERATOR
  
 PLEASE CLARIFY THE SCOPE OF THE ELECTRIC WORK PROPOSED.
 NEC 215.5
  
 PROVIDE A SINGLE LINE ELECTRICAL DIAGRAM SHOWING ALL
 CONDUIT AND WIRE SIZES INCLUDING THE EXISTING SERVICE
 AND METER.
 PROVIDE THE SPECIFICATIONS ON THE GENERATOR. VERIFY THE
 GENERATOR HAS A MAIN BREAKER. INDICATE THE PROXIMITY OF
 THE GENERATOR TO THE BUILDING.
 PROVIDE THE SPECIFICATIONS ON THE GENERATOR SLAB.
 PROVIDE THE SPECIFICATIONS ON THE AUTOMATIC TRANSFER
 SWITCH.
  
  