2012-07-14 20:10:191711 WORTHINGTON ROAD - BUILDING "A" & "B"
 PERMIT #12070414 & #12070422
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO- SUBMIT REVISION WITH THE FOLLOWING
 INFORMATION*****
  
 SUBMIT CUTSHEETS FOR EQUIPMENT TO BE INSTALLED.
  
 PROVIDE A SMOKE DETECTOR IN THE ELECTRICAL ROOM HOUSING
 THE NAC POWER EXTENDER.
  
 EACH BUILDING SHALL BE ANNUNCIATED SEPARATELY. PROVIDE
 A GRAPHIC ANNUNCIATOR (OR SIMILAR), THAT WILL ALLOW
 EMERGENCY RESPONDERS TO QUICKLY IDENTIFY IF THE ALARM
 CONDITION IS LOCATED IN BUILDING "A" OR BUILDING "B."
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 NOTE: WHERE THE FIRE ALARM CIRCUITS ENTER OR EXIT
 BUILDINGS, THE CIRCUITS AND EQUIPMENT SHALL BE
 INSTALLED IN ACCORDANCE WITH THE NEC (NFPA 70) SECTION
 760.32.
  