2012-07-17 09:22:492101 CENTERPARK DRIVE - WEST: SUITE #100
 PERMIT #12070404
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 THE EXIT DOORS UTILIZED ON LIFE SAFEY SHEET A-3 DO NOT
 MATCH THE EXIT DOORS AND EXIT SIGNS SHOWN ON SHEET E-2.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND/OR FIRE
 ALARM SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  