2012-07-17 09:57:032505 NORTH DIXIE HIGHWAY
 PERMIT #12070380
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS PERMIT SHOULD BE A PROPOSED CHANGE IN OCCUPANCY
 FROM MERCANTILE (MARKET ) TO ASSEMBLY (RESTAURANT).
  
 THE SEATING AREA IS APPROXIMATELY 1,050 SQUARE FEET
 WHICH EQUATES TO AN OCCUPANT LOAD OF 70 PERSONS BASED
 UPON AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON
 USING TABLES/CHAIRS.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 AN ASSEMBLY OCCUPANCY WILL REQUIRE TWO SEPARATE EXITS.
  
 THE PLANS INDICATE THIS BUILDING IS PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM. PLEASE CONFIRM AS OUR
 RECORDS DO NOT SHOW SPRINKLERS IN THIS BUILDING.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR; HOWEVER, THE MAIN ENTRY IS PERMITTED TO BE
 EQUIPPED PANIC HARDWARE OR WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
 SEPARATE PLANS AN PERMITS NEEDED FOR KITCHEN EXHAUST
 HOOD AND HOOD SUPPRESSION SYSTEM.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  