2012-07-17 09:57:03 | 2505 NORTH DIXIE HIGHWAY |
| PERMIT #12070380 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| THIS PERMIT SHOULD BE A PROPOSED CHANGE IN OCCUPANCY |
| FROM MERCANTILE (MARKET ) TO ASSEMBLY (RESTAURANT). |
| |
| THE SEATING AREA IS APPROXIMATELY 1,050 SQUARE FEET |
| WHICH EQUATES TO AN OCCUPANT LOAD OF 70 PERSONS BASED |
| UPON AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON |
| USING TABLES/CHAIRS. |
| |
| UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| AN ASSEMBLY OCCUPANCY WILL REQUIRE TWO SEPARATE EXITS. |
| |
| THE PLANS INDICATE THIS BUILDING IS PROTECTED BY AN |
| AUTOMATIC SPRINKLER SYSTEM. PLEASE CONFIRM AS OUR |
| RECORDS DO NOT SHOW SPRINKLERS IN THIS BUILDING. |
| |
| A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY |
| DOOR; HOWEVER, THE MAIN ENTRY IS PERMITTED TO BE |
| EQUIPPED PANIC HARDWARE OR WITH A KEYED LOCK WITH |
| LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE |
| DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO |
| OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. |
| |
| SEPARATE PLANS AN PERMITS NEEDED FOR KITCHEN EXHAUST |
| HOOD AND HOOD SUPPRESSION SYSTEM. |
| |
| DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE |
| SURFACE. |
| |
| PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF SPACE |
| BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE |
| ADJACENT EQUIPMENT. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |