2012-07-27 10:39:06 | BUILDING PLAN REVIEW |
| PERMIT: 12070380 |
| ADD: 2505 N DIXIE HWY |
| CONT: STONESTYLES |
| TEL: (561)809-5115 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE A LIFE DAFETY SHEET WITH A BREAK DOWN |
| OF AISLE WIDTHS WITH 2010 FBC-B 1017.4. ALSO PROVIDE AN |
| AREA BREAK DOWN FOR OCCUPANCY LOADS USING 15 NET FOR |
| UNCONCENTRATED TABLES AND CHAIRS, KITCHEN AREAS 200 |
| GROSS AND OFFICE SPACE 100 GROSS. IT APPEARS THE |
| OCCUPANT LOAD WILL BE GREATER THAN 50 OCCUPANTS MAKING |
| THIS A CHANGE OF OCCUPANCY TO A A-2 OCCUPANCY FOR |
| RESTARAUNTS. 2010 FBC-B TABLE 1004.1.1. |
| |
| WITH THIS BEING A CHANGE OF OCCUPANCY THE 2010 EXISTING |
| BUILDING CODE WILL APPLY, CHAPTER 9, |
| |
| 2) PLEASE PROVIDE A SURVEY OF THIS PROPERTY TO |
| DETERMINE IF THIS IS A SINGLE TENANT BUILDING UNDER |
| THIS PROPERTY CONTROL NUMBER, THIS DETERMINES WHICH |
| SECTION TO USE IN THE EXISTING BUILDING CODE: |
| 901.3 FOR WHERE THE WHOLE BUILDING IS UNDER GOING A |
| CHANGE OF OCCUPANCY OR |
| 901.3. FOR A PARTIAL CHANGE OF OCCUPANCY. |
| EACH HAS SEPERATE REQUIREMENTS. FOR THIS REVIEW WE WILL |
| USE WHOLE BUILDING UNDERGOING A CHANGE OF OCCUPANCY. |
| |
| 3) EXST BLDG CODE 904.1 FIRE PROTECTION REQUIREMENTS OF |
| SECTION 912 SHALL APPLY WHERE A BUILDING OR PORTIONS |
| THEREOF UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION. |
| EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A |
| CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES |
| AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED |
| ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL |
| BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| OCCUPANCY OCCURS. |
| |
| 4) EXST BLDG CODE 905.1 MEANS OF EGRESS IN PORTIONS OF |
| BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH SECTION 912. |
| 2010 FBC-B TABLE 1015.1 WILL REQUIRE TWO EXITS ISNCE |
| THE OCCUPANCY LOAD IS OVER 49 OCCUPANTS, PLEASE PROVIDE |
| THE 2ND EXIT. NOTE BUILDINGS THAT ARE SPRINKLERED SHALL |
| HAVE THEIR EXITS A MINIMUM OF 1/3 THE DIAGONAL APART. |
| FBC-B 1015.2.1. |
| |
| 5) ESXT BLDG CODE SECTION 906 ACCESSIBILITY ,906.1 |
| ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A |
| CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| THE PROVISIONS OF THE FLORIDA BUILDING CODE, |
| ACCESSIBILITY. |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| PLEASE PROVIDE COMPLIANCE WITH :202.4.1 |
| DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| NOTE THE EXISTING RESTROOM AT THE REAR OF THE |
| RESTARAUNT WILL NEED TO HAVE A RAMP TO BE ACCESSIBLE, |
| PROVIDE LANDING TOP & BOTTOM OF RAMP WILL REQUIRE |
| HANDRAILS IF RAMP IS OVER 6" IN HEIGHT. SEE 2010 |
| ACCESSIBILITY CODE 405 RAMP REQUIREMENTS 505 HANDRAILS. |
| |
| 6) SHEET 1.0A INDICATES THE USE OF NEW IN-SWINGING |
| BIFOLD DOORS, PLEASE PROVIDE PRODUCT TESTING REPORTS |
| FOR THIS PRODUCT. RULE 9N-3 (31)(A) EXTERIOR DOORS / |
| 2010 FBC-B 1609.6 |
| COMPONENTS & CLADDING, 1609.1.2 PROTECTION OF OPENINGS |
| & 1609.1.2.3 IMPACT RESISTANT COVERINGS. |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |
| |