Plan Review Notes
Plan Review Notes For Permit 12070359
Permit Number 12070359
Review Stop E
Sequence Number 1
Notes
Date Text
2012-07-13 09:03:4312070359
 200 CLEMATIS ST
 REVISION TO ELECTRICAL SERVICE
  
 PLEASE HAVE THE ELECTRICAL ENGINEER ADDRESS THE
 FOLLOWING REVIEW COMMENTS. PLEASE CALL IF THERE ARE ANY
 QUESTIONS:
  
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONE SERVICE UNLESS THERE ARE SPECIAL CONDITIONS.
 CLARIFY THE SPECIAL CONDITIONS PROMPTING THE NEW
 DESIGN. NEC 230.2, 230.71, 230.72
  
 MULTIPLE MAIN SERVICE DISCONNECTS WITHIN THE BUILDING
 MUST BE IDENTIFIED. NEC 230.2(E)
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 INDICATE THE SIZE AND LOCATION OF THE MAIN SERVICE
 BONDING JUMPER. NEC 250.24(B), 250.66
  
 INDICATE THE SIZE AND LOCATION OF THE DERIVED SYSTEM
 BONDING JUMPER. NEC 250.30(A)(1), 250.66
  
 INDICATE THE SIZE AND LOCATION OF THE GROUNDING
 ELECTRODE CONDUCTOR FOR THE DERIVED SYSTEM. NEC
 250.24(D)
  
 INDICATE THE INSULATION CLASS FOR THE 300 KVA
 TRANSFORMER. NEC 450.21 (B)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved