Plan Review Notes For Permit 12070359 |
Permit Number |
12070359 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-07-13 09:03:43 | 12070359 | | 200 CLEMATIS ST | | REVISION TO ELECTRICAL SERVICE | | | | PLEASE HAVE THE ELECTRICAL ENGINEER ADDRESS THE | | FOLLOWING REVIEW COMMENTS. PLEASE CALL IF THERE ARE ANY | | QUESTIONS: | | | | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED | | BY ONE SERVICE UNLESS THERE ARE SPECIAL CONDITIONS. | | CLARIFY THE SPECIAL CONDITIONS PROMPTING THE NEW | | DESIGN. NEC 230.2, 230.71, 230.72 | | | | MULTIPLE MAIN SERVICE DISCONNECTS WITHIN THE BUILDING | | MUST BE IDENTIFIED. NEC 230.2(E) | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 | | | | INDICATE THE SIZE AND LOCATION OF THE MAIN SERVICE | | BONDING JUMPER. NEC 250.24(B), 250.66 | | | | INDICATE THE SIZE AND LOCATION OF THE DERIVED SYSTEM | | BONDING JUMPER. NEC 250.30(A)(1), 250.66 | | | | INDICATE THE SIZE AND LOCATION OF THE GROUNDING | | ELECTRODE CONDUCTOR FOR THE DERIVED SYSTEM. NEC | | 250.24(D) | | | | INDICATE THE INSULATION CLASS FOR THE 300 KVA | | TRANSFORMER. NEC 450.21 (B) | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|