Plan Review Notes For Permit 12070319 |
Permit Number |
12070319 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-07-11 10:00:48 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- FLAT ROOF INFORMATION SUBMITTED: | | | | A) ACCORDING TO SEC. R301.2.1.4.3 OF | | FBC-2010-RESIDENTIAL, THIS BUILDING IS LOCATED ON | | EXPOSURE "D" NOT "C". ENGINEER TO REVISE RAS 117 | | CALCULATIONS AND BASE SHEET ENHANCED FASTENING AS | | REQUIRED. | | | | B) ENGINEER TO REVISE THE WIDTH OF THE PERIMETER AND | | CORNER AREAS. AS REQUIRED BY FIGURE R301.2(7) OF 2010 | | FBC-RESIDENTIAL THE WIDTH IS 4 FEET IN ALL CASES. SEE | | NOTE A. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR RIDGE VENT | | AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | [email protected] |
|