2012-07-11 10:00:48RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- FLAT ROOF INFORMATION SUBMITTED:
  
 A) ACCORDING TO SEC. R301.2.1.4.3 OF
 FBC-2010-RESIDENTIAL, THIS BUILDING IS LOCATED ON
 EXPOSURE "D" NOT "C". ENGINEER TO REVISE RAS 117
 CALCULATIONS AND BASE SHEET ENHANCED FASTENING AS
 REQUIRED.
  
 B) ENGINEER TO REVISE THE WIDTH OF THE PERIMETER AND
 CORNER AREAS. AS REQUIRED BY FIGURE R301.2(7) OF 2010
 FBC-RESIDENTIAL THE WIDTH IS 4 FEET IN ALL CASES. SEE
 NOTE A.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR RIDGE VENT
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS TO FBC.
  