Plan Review Notes
Plan Review Notes For Permit 12070252
Permit Number 12070252
Review Stop B
Sequence Number 1
Notes
Date Text
2012-07-10 11:45:40RE-ROOF REVISION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER RAS 117 CALCULATIONS SUBMITTED SPECIFY NOA
 #11-0510.03, SYSTEM TYPE A(1) ON PAGE 6-7 OF 14, WHILE,
 NOA 11-0510.03 SUBMITTED IS SHOWING SYSTEM TYPE E(1) ON
 PAGE 10 OF 14. INFORMATION NEEDS TO MATCH. SEC.
 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 2- GENERAL LIMITATION #5 ON PAGE 14 OF NOA 11-0510.03
 SUBMITTED SPECIFIES THAT IF THE FASTENER VALUE, AS
 FIELD-TESTED IS BELOW 275 LBF, THEN INSULATION
 ATTACHMENT SHALL NOT BE ACCEPTABLE. TEST REPORT TAS 105
 SUBMITTED SHOWS THAT THE FASTENER VALUE TESTED IS LESS
 THAN 275 LBF. THEREFORE, IT'S NOT ACCEPTABLE. SEC.
 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
 [email protected].