Plan Review Notes For Permit 12070252 |
Permit Number |
12070252 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-07-10 11:45:40 | RE-ROOF REVISION BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- ENGINEER RAS 117 CALCULATIONS SUBMITTED SPECIFY NOA | | #11-0510.03, SYSTEM TYPE A(1) ON PAGE 6-7 OF 14, WHILE, | | NOA 11-0510.03 SUBMITTED IS SHOWING SYSTEM TYPE E(1) ON | | PAGE 10 OF 14. INFORMATION NEEDS TO MATCH. SEC. | | 107.2.1.2 CITY AMENDMENTS TO FBC. | | | | 2- GENERAL LIMITATION #5 ON PAGE 14 OF NOA 11-0510.03 | | SUBMITTED SPECIFIES THAT IF THE FASTENER VALUE, AS | | FIELD-TESTED IS BELOW 275 LBF, THEN INSULATION | | ATTACHMENT SHALL NOT BE ACCEPTABLE. TEST REPORT TAS 105 | | SUBMITTED SHOWS THAT THE FASTENER VALUE TESTED IS LESS | | THAN 275 LBF. THEREFORE, IT'S NOT ACCEPTABLE. SEC. | | 107.2.1.2 CITY AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | [email protected]. |
|