Plan Review Notes
Plan Review Notes For Permit 12070060
Permit Number 12070060
Review Stop B
Sequence Number 3
Notes
Date Text
2012-08-15 21:00:05BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2010
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 ***THE COMMENT RESPONSE SUBMITTED ON 8/14/12 BY STEVE
 MORAGA, P.E., IS ACKNOWLEDGED. PLEASE RESPOND TO THE
 FOLLOWING COMMENTS WHICH FOLLOW THE SAME NUMBERING
 SEQUENCE AS THE PLAN REVIEW ON 8/1/12:
  
 1) FBC 2002.4 LOADS.
 THE SUBMITTED CALCULATIONS FROM SUNCOAST ARCHITECTURE &
 ENGINEERING:
 (B) THE UNITS OF MEASURE HAVE NOW BEEN CLARIFIED. THE
 VALUES FOR "ALLOWABLE STRESS DUE TO BENDING" AND
 "ALLOWABLE STRESS DUE TO COMPRESSION" STATED ON PAGES 1
 AND 2 OF THE "ENGINEERING CALCULATIONS" APPEAR TOO HIGH
 FOR 6061T6 ALUMINUM. PLEASE STATE THE SOURCE OF THE
 STATED ALLOWABLE STRESS VALUES.
 (E) THE COMMENT RESPONSE LETTER STATES THAT THE MOMENT
 DISTRIBUTION CALCULATION HAS BEEN SUBMITTED TO SHOW
 THAT USING THE SUM OF THE MOMENTS ON EACH BEAM SEGEMENT
 IS A CONSERVATIVE APPROACH. THE LATTER IS NOT A TYPICAL
 METHOD OF ANALYSIS, SO THE MOMENT DISTRIBUTION
 CALCULATION IS VERY RELEVANT. THE DIAGRAMS ON PAGE 3
 AND 7 OF THE "MOMENT DISTRIBUTION CALCULATION"
 CORRECTLY SHOW THAT JOINT 1 IS THE CONNECTION TO THE
 HOST STRUCTURE. THAT CONNECTION IS SHOWN IN DETAIL
 G/A-3 OF THE PROJECT PLANS A PINNED CONNECTION WHICH IS
 TYPICAL. AS SUCH THE CONNECTION DOES NOT AND SHOULD NOT
 TRANSFER MOMENT TO THE HOST STRUCTURE. THAT IS A FACT
 THAT IS NOT RECOGNIZED OR CORRECTLY MODELLED IN MOMENT
 DISTRIBUTION CHART ON PAGE 5 OF THE CALCULATIONS, WHICH
 CLAIMS A 717 FT # (OR 8.6 KP IN.) MOMENT AT THAT
 CONNECTION. THE MOMENT AT THAT PINNED CONNECTION SHOULD
 BE ZERO WHICH MEANS THAT THE STATED 753 FT # MOMENT AT
 THE OTHER END OF THAT SECTION OF THE BEAM IS
 SIGNIFICANTLY UNDERESTIMATED WHICH IN TURN MEANS THAT
 THE SPAN MOMENTS ON THE BEAM ARE ALSO SIGNIFICANTLY
 UNDERESTIMATED. THEREFORE MOMENT DISTRIBUTION
 CALCULATION AS IT STANDS DOES NOT CLEARLY SHOW THAT
 USING THE SUM OF THE MOMENTS ON EACH BEAM SEGEMENT IS A
 CONSERVATIVE APPROACH. PLEASE ADDRESS THIS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS