Plan Review Notes
Plan Review Notes For Permit 12070060
Permit Number 12070060
Review Stop B
Sequence Number 1
Notes
Date Text
2012-07-25 16:54:19****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FBC RESIDENTIAL 301.1 (RESISTANCE TO WIND):
  
 1. REGARDING BEAM SPAN CALCULATIONS, SHEET 1, PLEASE
 REVISE TO INCLUDE THE VALUE FOR 'L'. THIS APPLIES TO
 CENTER MANSARD SPAN, WINDWARD MANSARD LEG, AND LEEWARD
 MANSARD LEG. CALCULATION IS PROVIDED BUT REFERS TO WL,
 PLEASE PROVIDE SPANS (DIMENSION OF L).
  
 2. BASED ON LAT/LONG LOCATION, THIS PROJECT APPEARS TO
 BE IN THE 152 MPH WIND ZONE (WWW.ATCOUNCIL.ORG). EITHER
 PROVIDE INFORMATION TO SHOW HOW ENGINEER HAS DETERMINED
 WIND SPEED, OR REVISE PLAN TO A MINIMUM OF 152MPH.
  
 IF OTHER COMMENTS ARE ADDRESSED AND PLANS DO NOT NEED
 TO BE REVISED, A LETTER FROM ENGINEER THAT THIS DESIGN
 COMPLIES WITH 152MPH WILL SUFFICE.
  
 3. DUE TO THE DELAY IN FIRST PLAN REVIEW, ENGINEER MAY
 PROVIDE THIS INFORMATION VIA EMAIL FOR PRELIMINARY
 REVIEW TO DETERMINE WHETHER ADDITIONAL INFORMATION IS
 REQUIRED. BEAMS APPEAR OVERSTRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.