Notes
Date Text
2012-07-11 09:46:30****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****PROVIDE REVISED INSTALLATION SCHEDULE AND FLOOR
 PLAN AT INSPECTION****
 ****SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION
 MAY BE REQUIRED****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 301.1, FAC9N-3, PLEASE REVISE THE INSTALLATION
 SCHEDULE (FOR THE ACCORDION SHUTTERS) TO ADDRESS THE
 FOLLOWING ISSUES:
  
 SUBSTRATE IS NOTED AS "CONCRETE BLOCK" BUT ANCHORING
 FROM "CONCRETE" SUBSTRATE WAS USED, SEE SHEET 11. FOR
 FILLED CELLS (GROUT FILLED BLOCK) OR HOLLOW BLOCK, USE
 THE "HOLLOW BLOCK" CHART ON THE SAME PAGE.
  
 2.5" EDGE DISTANCE REQUIRED, 2" PROPOSED. SEE SHEET 11,
 ANCHOR CHART.
  
 1 3/4" EMBEDMENT FOR TAPCON REQUIRED, 1 3/4" PROPOSED.
 DUE TO STUCCO, PRODUCT THICKNESS, A LONGER FASTENER IS
 REQUIRED.
  
 2. PROVIDE A FLOOR PLAN SHOWING LOCATION OF WINDOW,
 SHUTTER, DOOR INSTALLATION.
  
 INSTRUCTIONS TO CONTRACTOR - REVISE INSTALLATION
 SCHEDULE AS INDICATED
 PROVIDE INSTALLATION SCHEDULE AND FLOOR PLAN TO FIELD
 INSPECTOR - SUBJECT TO INSPECTOR'S DISCRETION, REVISED
 INSTALLATION SCHEDULE MAY BE ACCEPTED IN THE FIELD OR A
 REVISION MAY BE REQUIRED
  
 DISCUSSED WITH AND AGREED TO BY CONTRACTOR
  
  
  
  