Plan Review Notes
Plan Review Notes For Permit 12060899
Permit Number 12060899
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-07-31 11:35:001500 BELVEDERE ROAD
 PERMIT #12060899
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMPLIED: PROVIDE PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 REPEAT COMMENT: PROVIDE BUILDING ADDRESS VISIBLE FROM
 THE STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING
 AND BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE
 AND SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: PROVIDE A FLOOR PLAN SHOWING EXIT
 DOORS, LIGHTING, ETC. FOR THE EASTERN MOST PORTION OF
 THE BUILDING INDICATED AS "NO WORK THIS AREA." INDICATE
 THE USE OF THIS SPACE.
  
 REPEAT COMMENT: INDICATE IF ANY VEHICLE REFUELING OR
 VEHICLE MAINTENANCE/REPAIRS/BODYWORK/PAINTING IS
 INTENDED FOR THIS FACILITY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730