2012-07-10 09:34:531500 BELVEDERE ROAD
 PERMIT #12060899
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2
 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1).
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE A FLOOR PLAN SHOWING EXIT DOORS, LIGHTING, ETC.
 FOR THE EASTERN MOST PORTION OF THE BUILDING INDICATED
 AS "NO WORK THIS AREA." INDICATE THE USE OF THIS SPACE.
  
 INDICATE IF ANY VEHICLE REFUELING OR VEHICLE
 MAINTENANCE/REPAIRS/BODYWORK IS INTENDED FOR THIS
 FACILITY.
  