2012-07-19 09:10:45 | BUILDING PLAN REVIEW |
| PERMIT: 12060899 |
| ADD: 1500 BELVEDERE RD |
| CONT: GARLAND BROWN |
| TEL: (561)719-8015 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES THE CONTRACT VALUE |
| OF $42,500.00, PLEASE SEE THE CODE SECTION LISTED BELOW |
| THAT DEALS WITH ACCESSIBILITY TO EXISTING BUILDINGS AND |
| THE |
| ADDITIONAL COST INVOLVED TO START TO BRING THIS |
| STRUCTURE UP TO THE CURRENT ACCESSIBILITY STANDARDS. |
| THE 2010 FBC-ACCESSIBILITY CODE SECTION 202.4.1 |
| REQUIRES UP TO 20% OF THE CONTRACT VALUE ($8,500) TO |
| BRING THE BUILDING UP TO CODE FOR ACCESSIBILITY. |
| SECTION 202.4.2 PROVIDES THE PRIORITY IN WHICH ELEMENTS |
| SHOULD BE MADE ACCESSIBLE WITHOUT INCURRING OVER THE |
| 20% DISPROPORTIONATE COST. |
| 202.4.1 DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 1A) INTERIOR DOORS ARE LABELED AS 2'8" WIDE DOORWAYS, |
| 2010 ACCESSIBILITY CODE 404.2.3 REQUIRES A CLEAR WIDTH |
| OF 32" WHICH REQUIRES AT A MINIMUM OF 34". |
| 404.2.3 CLEAR WIDTH. |
| DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES |
| (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH |
| SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| OPENINGS MORE THAN 24 INCHES (610 MM) DEEP SHALL |
| PROVIDE A CLEAR OPENING OF 36 INCHES (915 MM) MINIMUM. |
| THERE SHALL BE NO PROJECTIONS INTO THE REQUIRED CLEAR |
| OPENING WIDTH LOWER THAN 34 INCHES (865 MM) ABOVE THE |
| FINISH FLOOR OR GROUND. PROJECTIONS INTO THE CLEAR |
| OPENING WIDTH BETWEEN 34 INCHES (865 MM) AND 80 INCHES |
| (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL NOT |
| EXCEED 4 INCHES (100 MM). |
| |
| 1B) PLEASE PROVIDE A LIST OF ALTERATIONS PROVIDING |
| WHERE THE MONIES WILL BE SPENT BRINGING THIS BUILDING |
| UP TO THE 2010 ACCESSIBILITY CODE. |
| |
| 2) PLEASE PROVIDE LOCATTION FOR PORTABLE FIRE |
| EXTINGUISHERS PER 2010 FBC-B: |
| 906.5 CONSPICUOUS LOCATION. [F] |
| |
| PORTABLE FIRE EXTINGUISHERS SHALL BE LOCATED IN |
| CONSPICUOUS LOCATIONS WHERE THEY WILL BE READILY |
| ACCESSIBLE AND IMMEDIATELY AVAILABLE FOR USE. THESE |
| LOCATIONS SHALL BE ALONG NORMAL PATHS OF TRAVEL, UNLESS |
| THE FIRE CODE OFFICIAL DETERMINES THAT THE HAZARD POSED |
| INDICATES THE NEED FOR PLACEMENT AWAY FROM NORMAL PATHS |
| OF TRAVEL. |
| |
| 906.6 UNOBSTRUCTED AND UNOBSCURED. [F] |
| |
| PORTABLE FIRE EXTINGUISHERS SHALL NOT BE OBSTRUCTED OR |
| OBSCURED FROM VIEW. IN ROOMS OR AREAS IN WHICH VISUAL |
| OBSTRUCTION CANNOT BE COMPLETELY AVOIDED, MEANS SHALL |
| BE PROVIDED TO INDICATE THE LOCATIONS OF EXTINGUISHERS. |
| |
| 3A)EXIT SIGNS 2010 FBC-B 1006.3.1: EXITS SHALL BE |
| MARKED BY AN APPROVED SIGN READILY VISIBLE FROM ANY |
| DIRECTION OF EXIT ACCESS. EVERY EXIT SIGN SHALL BE |
| SUITABLY ILLUMINATED BY A RELIABLE LIGHT SOURCE. |
| EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS SHALL BE |
| VISIBLE IN BOTH NORMAL AND EMERGENCY LIGHTING. |
| |
| 3B) 1006.3.4 EXIT STAIR DOOR OR TACTILE SIGNAGE. |
| TACTILE SIGNAGE STATING "EXIT" AND COMPLYING WITH |
| ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR |
| ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL |
| BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60 |
| INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER |
| LINE OF THE SIGN. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |