Plan Review Notes
Plan Review Notes For Permit 12060867
Permit Number 12060867
Review Stop B
Sequence Number 1
Notes
Date Text
2012-07-18 09:00:56DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH FBC R806.1 FOR REQUIRED ROOF
 VENTILATION.
  
 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS THAT HAVE
 BEEN SIGNED BY THE PREPARER AND THE OWNER AGENT AS
 REQUIRED BY FBC ENERGY CONSERVATION SECTION 401.2.
  
 3) SPECIFY THE SIZES OF THE ROOF SCUPPERS AND OVERFLOW
 SCUPPERS ON SHEET S.01 OF THE PLANS. FBC R903.4.1 AND
 FBC PLUMBING 1106.7 AND 1107.3
  
 4) THE COMPONENT AND CLADDING PRESSURES ON SHEET S.01
 IS SPECIFIED AS + / - 64 PSF WORST CASE AND A 6 FEET
 MINIMUM EDGE STRIP. HOWEVER, THE DIAGRAM AND ANOTHER
 LOCATION SPECIFIES EDGE ZONE PRESSURES AS + 49.42 PSF
 AND - 66.08 PSF. THE PRODUCT APPROVAL DESIGN PRESSURES
 FOR THE DOORS AND WINDOWS ARE + 55 PSF AND - 65 PSF.
 THE + 64 PSF FROM THE FIRST AND THE - 66.08 PSF EXCEEDS
 THE DESIGN PRESSURES OF THE PRODUCT APPROVALS. PLEASE
 CLARIFY AND PROVIDE THE COMPONENT AND CLADDING
 PRESSURES THAT ARE SPECIFIC TO THIS PROJECT. CITY
 AMENDMENTS 107.2.1 AND FBC R301.2.1
  
 5) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CLAY ROOF TILE AND PROVIDE TWO COPIES OF
 APPROVALS FOR THE ADHESIVE OR MORTAR PRODUCT THAT WILL
 BE USED. FBC R905.3.7
  
 6) SPECIFY THE FASTENING OPTION FROM THE PRODUCT
 APPROVAL THAT WILL BE USED TO INSTALL THE GAF MODIFIED
 BITUMEN ROOF SYSTEM AND SUBMIT TWO COPIES OF SIGNED AND
 SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING AT
 THE CORNER AND PERIMETER AREAS AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 31 OF THE NOA. FBC R905.11
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]