Date |
Text |
2012-07-12 08:37:28 | BUILDING PLAN REVIEW |
| PERMIT: 12060838 |
| ADD: 5200 N FLAGLER DR #1901 |
| CONT: A& A DEVELPOMENT |
| TEL: (561)719-0895 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION : DENIED |
| PLANS DO NOT INDICATE THE REMOVAL OF FLOORING, IF FLOOR |
| COVERINGS ARE TO BE REMOVED THEN COMPLIANCE WITH : |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1A) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE |
| MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR |
| TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND |
| IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| 603.1.3.2 EXCEPTIONS: |
| 1 INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| 200. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |