Notes |
Date |
Text |
2012-06-30 17:55:39 | 1001 SOUTH FLAGLER DRIVE | | PERMIT #12060781 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SHEET 9 OF 12: PROVIDE AN ADDITIONAL NOTIFICATION | | APPLIANCE FOR THE SOUTHEAST AREA OF THE POOL DECK. | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | CODE CHANGE ALERT: EXISTING APARTMENT BUILDINGS NOT | | PROTECTED BY AUTOMATIC SPRINKLERS OR A COMPLETE | | AUTOMATIC SMOKE DETECTION SYSTEM SHALL HAVE SINGLE | | STATION OR MULTI-STATION SMOKE ALARMS (HARD-WIRED OR | | BATTERY POWERED) INSTALLED INSIDE EACH BEDROOM AND | | DIRECTLY OUTSIDE BEDROOM DOORS. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | |
|