2012-07-09 15:46:54 | BUILDING PLAN REVIEW |
| PERMIT: 12060539 |
| ADD: 1801 S FLAGLER # 1602 |
| CONT: MARYJULE CONSTRUCTION, INC |
| TEL: (561)386-6032 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET # 1 INDICATES NEW EXTERIOR WINDOWS AND SLIDING |
| GLASS DOORS. NO PRODUCT TESTING REPORTS WERE SUBMITTED, |
| NOTED THIS UNIT IS LOCATED ON THE 16TH FLOOR AND WILL |
| ONLY NEED TO COMPLY FOR WIND. |
| COMPONENTS & CLADDING 2010 FBC-B 1609.6.4.4.1. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| TABLE 1609.2(2) . |
| |
| 4) THE PERMIT APPLICATION INDICATES NEW FLOORS AND THE |
| PLANS INDICATE THE USE OF "EASY MAT" SOUND PROOFING, |
| PLAESE PROVIDE CODE COMPLIANCE FOR; |
| 3A) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| 3B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE |
| MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR |
| TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND |
| IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| 603.1.3.2 EXCEPTIONS: |
| 1 INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| 200. |
| |
| 5) SHEET 1 INDICATES THE CEILINGS ARE TO BE FURRED DOWN |
| 3/4" WITH 3/4" FURRING CHANNELS, IS THIS HI-HAT |
| MATERIAL AND IF SO HOW OFTEN IS THE HI-HAT TO BE |
| FASTENED AND WITH WHAT TYPE OF FASTENER? ADDITIONAL |
| INFORMATION REQUIRED 107.2.1.3. |
| |
| 6) SHEET 1 INDICATES THE REMOVAL OF TUB AND THE |
| INSTALATION OF A NEW SHOWER, PLEASE PROVIDE |
| DOCUMENTATION FOR CODE COMPLIANCE FOR: |
| 2010 FBC-B 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT |
| OR GLASS MAT GYPSUM BACKERS IN COMPLIANCE WITH ASTM C |
| 1178, C 1288 OR C 1325 AND INSTALLED IN ACCORDANCE WITH |
| MANUFACTURER RECOMMENDATIONS SHALL BE USED AS A BASE |
| FOR WALL TILE IN TUB AND SHOWER AREAS AND WALL AND |
| CEILING PANELS IN SHOWER AREAS. WATER-RESISTANT GYPSUM |
| BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER |
| CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE |
| WITH GA-216 OR ASTM C 840 AND MANUFACTURER |
| RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED |
| UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING |
| AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM |
| C 840. |
| |
| 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING |
| BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS: |
| 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| COMPARTMENTS. |
| 2 . WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |