Plan Review Notes For Permit 12060468 |
Permit Number |
12060468 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-06-18 17:01:41 | RESIDENTIAL RE-ROOF BUILDING REVIEW COMMENTS. | | 2010 FBC. | | | | 1- THIS IS A QUADRUPLEX AND ALL FOUR UNITS ARE SHARING | | THE SAME ROOF. NEED TO RE-ROOF ENTIRE ROOF AS REQUIRED | | BY SEC. 611.1.1 OF 2010 FBC-EXISTING BUILDING. | | | | 2- NEED SEPARATE PERMIT FOR THE ROOF A/C UNITS REMOVAL | | AND REPLACEMENT TO VERIFY COMPLIANCE WITH THE WIND | | RESISTANCE AS REQUIRED BY SEC. M1307.2.1. | | | | 3- CONTRACTOR TO REVISE THE BUILDING MEAN ROOF HEIGHT. | | THIS IS A TWO STORY BUILDING. THEREFORE 12'-0" MRH IS | | INCORRECT. SEC. 107.2.1 OF CITY AMENDMENTS TO FBC. | | | | 4- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7 ON NOA 12-0227.18 SUBMITTED. NEED RAS 117 | | CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY | | SEC. R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE. | | ***NOTE; TAKE INTO CONSIDERATION THAT THIS BUILDING IS | | LOCATED ON EXPOSURE "C". | | | | 5- SPECIFY WHICH BASE SHEET FASTENING OPTION ON PAGE 14 | | OF NOA SUBMITTED IS GOING TO BE USED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301.2.1.4.3 AND RAS 117 CALCULATIONS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|