Plan Review Notes For Permit 12060395 |
Permit Number |
12060395 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-06-15 14:50:57 | RE-ROOF BUILDING REVIEW COMMENTS. | | 2010 FBC. | | | | 1- PROVIDE 2 COPIES OF ENGINEER'S LETTER. AND, | | ENGINEER'S LETTER NEEDS TO HAVE THE ENGINEER'S ORIGINAL | | SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTES. | | | | 2- PROVIDE 2 COPIES OF THE NOA 11-0425.07. AND, CLEARLY | | IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA 11-0425.07 | | SUBMITTED IS GOING TO BE USED TO VERIFY COMPLIANCE WITH | | THE DESIGN PRESSURES OF SEC. 1609 AND ENGINEER'S | | CALCULATIONS. | | | | 3- SPECIFY TOTAL SQUARE FOOTAGE OF ROOF AREA TO BE | | RE-ROOFED. ARE THE THREE FLAT ROOF AREAS SHOWN ON THE | | PROPERTY APPRAISAL WEBSITE GOING TO BE RE-ROOFED.?. | | NEED TO VERIFY COMPLIANCE WITH VALUE STATED IN THE | | REVISION FORM. SEC. 109.3 CITY AMENDMENTS TO FBC. | | | | 4- STRUCTURAL REPAIRS SPECIFIED BY THE ENGINEER NEED TO | | BE DONE UNDER A SEPARATE SUBPERMIT. WORK TO BE | | PERFORMED BY CONTRACTOR WITH PROPER LICENSE AS REQUIRED | | BY CHAPTER 489 FLORIDA STATUTE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|