2012-07-25 13:29:18 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) CORRECTED. |
| |
| 2) CORRECTED. |
| |
| 3) CORRECTED. HOWEVER, THE DOOR SCHEDULE LISTS TWO |
| STATE PRODUCT APPROVAL NUMBERS FOR THE AMARR GARAGE |
| DOOR. THE PRODUCT APPROVAL PRESSURES (-52.1, +45.9 PSF) |
| LISTED IN THE SCHEDULE ARE FOR FL #7170-R3. ACCORDING |
| TO THE PRODUCT EVALUATION, FL #6243 HAS PRESSURES OF |
| (-41.0, +37.0 PSF) WHICH ARE LESS THAN THE REQUIRED |
| OPENING PRESSURES SPECIFIED IN THE DOOR SCHEDULE. |
| PLEASE CORRECT. CITY AMENDMENTS 107.2.1 AND R301.2.1 |
| |
| 4) CORRECTED. |
| |
| 5) CORRECTED. |
| |
| 6) CORRECTED. |
| |
| 7) CORRECTED. |
| |
| 8) SUBMIT CURRENT PRODUCT APPROVALS FOR THE EXTERIOR |
| DOORS, WINDOWS, ROOFING MATERIAL, LINTELS AND OTHER |
| COMPONENTS AND CLADDING REQUIRED BY DCA RULE 9N-3. |
| PRODUCT APPROVALS FOR THE ROOFING MATERIAL, LINTELS AND |
| TRUSS ANCHORS HAVE NOT BEEN SUBMITTED. ALSO, PLEASE |
| SUBMIT THE FL COVERSHEET AND EVALUATION REPORT FOR THE |
| FIBERGLASS ENTRY DOOR. |
| |
| 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR |
| EVALUATIONS FOR THE SPRAY FOAM INSULATION, FIRE |
| RETARDANT COATING AND HUBER ROOF SHEATHING. |
| |
| 10) CORRECTED. |
| |
| 11) THE WINDLOADS SPECIFIED IN THE TABLE ON SHEET S-3 |
| NEEDS TO MATCH THE OPENING PRESSURES SPECIFIED IN THE |
| WINDOW AND DOOR SCHEDULES ON THE ARCHITECTURAL |
| DRAWINGS. CITY AMENDMENTS 107.2.1 AND FBC R301.2.1 THE |
| SLIDING GLASS DOOR AND OVERHEAD GARAGE DOOR PRESSURES |
| DO NOT MATCH. ALSO, IN THE DOOR SCHEDULE THE POSITIVE |
| PRESSURE IS MORE THAN THE NEGATIVE PRESSURE FOR THE |
| SLIDING GLASS DOOR. THE NEGATIVE PRESSURE IS ALWAYS |
| HIGHER. PLEASE CORRECT. |
| |
| 12) THE FLOOR PLAN, ROOF PLAN AND ELEVATIONS THAT WERE |
| SUBMITTED ARE ALL FOR A 6 UNIT BUILDING. IF YOU WISH TO |
| USE THIS MASTER FOR BUILDINGS WITH OTHER THAN SIX UNITS |
| YOU WILL NEED TO SUBMIT FLOOR PLANS, ROOF PLANS AND |
| ELEVATIONS FOR EACH OF THE DIFFERENT CONFIGURATIONS. |
| CITY AMENDMENTS 107.2.1 |
| |
| 13) NEW COMMENT. ON SHEET S-3 THE INTERIOR AND CORNER |
| ZONE PRESSURES FOR THE ENTRY DOOR ARE THE SAME. THE |
| CORNER ZONE PRESSURES SHOULD BE HIGHER. PLEASE CORRECT. |
| FBC R301.2.1 |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |