| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA |
| FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF |
| BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| |
| ALL NEW APARTMENTS AND TOWNHOUSES SHALL BE PROTECTED |
| THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| SPRINKLER SYSTEM PER SECTION 30.3.5.1 (NFPA 101 - |
| FLORIDA EDITION 2009). |
| |
| FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| SEALED (BY DESIGN PROFESSIONAL) FIRE PROTECTION |
| CONSTRUCTION DOCUMENTS FOR THE DESIGN OF 50 OR MORE |
| AUTOMATIC FIRE SPRINKLERS. |
| |
| FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| |
| PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| |
| |
| |
| |
| |