2012-06-29 12:29:462010 FBC
  
 DENIED BY BUILDING
  
 1) ON PLAN SHEET T-1, THE STRUCTURAL NOTES SPECIFY ASCE
 7-05 AND A WINDSPEED OF 175 MPH. THE 2010 FBC
 REFERENCES ASCE 7-10 AND THE WINDSPEED FOR RISK
 CATEGORY II IS 170 MPH. FBC CHAPTER 43 AND FBC
 R301.2.1.1
  
 2) PLEASE UPDATE THE FOLLOWING STANDARDS SPECIFIED ON
 T-1 TO THE 2008 EDITIONS. ACI 318, ACI 530, ASCE 5, AND
 TMS 402. FBCR CHAPTER 43
  
 3) THE PRODUCT APPROVAL INFORMATION IN THE DOOR AND
 WINDOW SCHEDULE NEED TO BE BROUGHT CURRENT. ALL OF THEM
 HAVE EXPIRED, BEEN SUPERSEDED OR BEEN REVISED. DCA RULE
 9N-3
  
 4) THE REQUIRED OPENING PRESSURES LISTED IN THE
 SCHEDULE FOR DOOR NUMBER 2 ARE HIGHER THAN THE ONES
 INDICATED FROM THE PRODUCT APPROVAL. PLEASE CORRECT.
 FBC R301.2.1
  
 5) PLEASE REVIEW ALL NEW PRODUCT APPROVAL DESIGN
 PRESSURES AGAINST THE REQUIRED OPENING PRESSURES TO
 VERIFY COMPLIANCE WITH FBC R301.2.1
  
 6) IN THE DOOR SCHEDULE ON SHEET TU-1.0 THE REMARKS FOR
 DOOR 2 HAVE BEEN PRINTED OVER AND ARE NOT LEGIBLE.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. CITY AMENDMENTS
 107.3.4.1
  
 8) SUBMIT CURRENT PRODUCT APPROVALS FOR THE EXTERIOR
 DOORS, WINDOWS, ROOFING MATERIAL, LINTELS AND OTHER
 COMPONENTS AND CLADDING REQUIRED BY DCA RULE 9N-3.
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR
 EVALUATIONS FOR THE SPRAY FOAM INSULATION, FIRE
 RETARDANT COATING AND HUBER ROOF SHEATHING.
  
 10) ON SHEET S-1 IN THE DESIGN PARAMETERS AND
 ASSUMPTION TABLE UNDER BUILDING HEIGHT ASCE 7-05 IS
 SPECIFIED. PLEASE UPDATE TO ASCE 7-10. FBCR CHAPTER 43
  
 11) THE WINDLOADS SPECIFIED IN THE TABLE ON SHEET S-3
 NEEDS TO MATCH THE OPENING PRESSURES SPECIFIED IN THE
 WINDOW AND DOOR SCHEDULES ON THE ARCHITECTURAL
 DRAWINGS. CITY AMENDMENTS 107.2.1 AND FBC R301.2.1
  
 12) THE FLOOR PLAN, ROOF PLAN AND ELEVATIONS THAT WERE
 SUBMITTED ARE ALL FOR A 6 UNIT BUILDING. IF YOU WISH TO
 USE THIS MASTER FOR BUILDINGS WITH OTHER THAN SIX UNITS
 YOU WILL NEED TO SUBMIT FLOOR PLANS, ROOF PLANS AND
 ELEVATIONS FOR EACH OF THE DIFFERENT CONFIGURATIONS.
 CITY AMENDMENTS 107.2.1
  