Plan Review Notes
Plan Review Notes For Permit 12060374
Permit Number 12060374
Review Stop P
Sequence Number 1
Notes
Date Text
2012-07-16 14:18:54FBC PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A0.0 SHOWS TOTAL OCCUPANCY OF 3508 OCCUPANTS.
 FBC PLUMBING 2010 403.1.1 TO DETERMINE THE OCCUPANT
 LOAD OF EACH SEX THE TOTAL OCCUPANT LOAD SHALL BE
 DIVIDED IN HALF.
 TABLE 403.1 MERCANTILE 1754 MEN WOULD REQUIRE 4 WATER
 CLOSETS OR UP TO 50% URINALS, WOMEN 4 WATER CLOSETS,
 AND ONE UNISEX TOILET PER 403.5. TOTAL = 9
 PLEASE LIST THE EXISTING FIXTURES TO COMPARE WITH THE
 REQUIRED FACILITIES FOR THE COMBINED BUILDINGS.
  
 2. SHEET P2.1 FOR THE CAFE AREA A GREASE TRAP OR
 INTERCEPTOR MAY BE REQUIRED DEPENDING UPON WHAT IS
 BEING PREPARED.
 1003.3.1 A GREASE INTERCEPTOR OR AUTOMATIC GREASE
 REMOVAL DEVICE SHALL BE REQUIRED TO RECEIVE THE
 DRAINAGE FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN
 WASTE LOCATED IN FOOD PREPARATION AREAS... THAT ALLOW
 FATS, OILS OR GREASE TO BE DISCHARGED.
  
 ADVISORY:
 IRRIGATION IS NOT PART OF THIS REVIEW. A SEPARATE
 APPLICATION, PLAN. REVIEW, AND PERMIT WILL BE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  