2012-06-23 20:26:11 | 2101 PALM BEACH LAKES BOULEVARD |
| 107,000 SQ.FT. CLASS "A" MERCANTILE OCCUPANCY |
| PERMIT #12060374 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| FIRE LANES SHALL BE HAVE PAINTED CURB MARKINGS AND BE |
| MARKED WITH FREESTANDING SIGNS READING, "FIRE LANE - NO |
| PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL |
| BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS |
| AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE |
| BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE |
| TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART. |
| FLORIDA FIRE PREVENTION CODE SECTION 18.2.3.5.3. |
| |
| TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE |
| SITE DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN |
| DESIGNATED EXTERIOR AREAS. ALL OTHER DEMOLITION OR |
| CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" SIGNS |
| POSTED. |
| |
| WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR |
| SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY |
| EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL |
| EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED |
| WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. |
| |
| EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED |
| IN THE USE OF PORTABLE FIRE EXTINGUISHERS. |
| |
| SHEET A2.3: FOR CLASS A MERCANTILE OCCUPANCIES, PROVIDE |
| AND MAINTAIN AT LEAST ONE AISLE 60-INCHES WIDE LEADING |
| DIRECTLY TO AN EXIT. |
| |
| SHEET A2.3: PROVIDE PERMANENT BOLLARDS IN ADDITION TO |
| FLOOR MARKINGS FOR THE 44-INCH WIDE EGRESS AISLE |
| LOCATED IN THE STOCKROOM/STAGING AREA. |
| |
| SHEET C4: FIRE HYDRANTS SHALL BE PROVIDED WITH |
| CLEARANCES OF 7'-6" TO THE FRONT AND SIDES AND 4' TO |
| THE BACKSIDE PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA |
| EDITION. THESE CLEARANCES MAY AFFECT A FEW PARKING |
| SPACES. |
| |
| SHEET FS1.1: CITY FURNITURE AND ASHLEY FURNITURE ARE |
| LOCATED IN SEPARATE, STAND-ALONE BUILDINGS SHARING A |
| COMMON 4-HOUR FIRE WALL; THEREFORE, EACH BUILDING NEEDS |
| ITS OWN FIRE WATER SERVICE, BACKFLOW PREVENTER AND |
| SPRINKLER SYSTEM. |
| |
| SHEET FS2.1: THE CONSTRUCTION DOCUMENTS ESTABLISH |
| MIRCEA PELLA AS THE ENGINEER OF RECORD FOR THE FIRE |
| SPRINKLER DESIGN, THEREFORE, THE SPRINKLER SHOP |
| DRAWINGS SHALL NOT BE SIGNED/SEALED BY THE CONTRACTOR'S |
| ENGINEER. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| |