2012-07-13 10:44:44 | BUILDING PLAN REVIEW |
| PERMIT:12060374 |
| ADD: 2101 PALM BEACH LAKES |
| CONT: MILLER |
| TEL: (954)605-2193 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) A RESIDENT INSPECTOR WILL BE REQUIRED FOR THIS |
| PROJECT PER WEST PALM BEACH ADMINISTRATIVE CODE |
| SECTION: |
| 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A |
| CERTIFICATE CALLED FOR BY ANY PROVISION OF THE |
| TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS |
| UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A |
| RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| SERVICE IN THE FOLLOWING INSTANCES: |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE |
| INCH |
| 4. FOR PILE DRIVING |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| METHODS OF CONSTRUCTION |
| SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| THE RESIDENT INSPECTOR. |
| CONTACT KEN CONRAD MANAGER OF THE RESIDENT INSPECTOR |
| PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 2) THE STRUCTURAL SHEETS S-5.3 & S-5.4 BOTH INDICATE |
| TILT WALL DESIGN WHERE WALL SECTIONS ARE ELEVATED AAND |
| BOLTED TO OTHER WALL SECTIONS BELOW WITHOUT THE USE OF |
| A HAUNCH BEAM, PLEASE PROVIDE STRUCTURAL CALCULATIONS |
| FOR THE LOADSTO BE RESISTED FOR THE UPPER PORTION OF |
| THIS WALL SECTION, FOR GRAVITY LOADS, UPLIFT LOADS & |
| LATERAL LOADS. |
| 2010 FBC-B 1901.4 CONSTRUCTION DOCUMENTS. |
| |
| 3) SHEET A-1.1 THE LIGHT POLE APPEARS TO BE WITHIN THE |
| ACCESSIBLE WALKWAY, DROPED CURB SECTION , PLEASE REVIEW |
| SECTION 11-405.1. |
| |
| 4) SHEET A2.2 AT DOOR OPENING # 6, THE NEW FIRE RATED |
| TILT WALL STOPS SHORT OF THE DOOR OPENING. TABLE 602 |
| VERSES SECTION 503.1. SHEET A2.1 INDICATES A SECTION OF |
| WALL FROM THE EXISTING BUILDING AS A 4 HR FIRE RATED |
| WALL AND A NEW SECTION OF TILT WALL AS A 4 HR RATED |
| SECTION OF WALL. |
| A) TBEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION.HE EXISTING BUILDING APPEARS TO HAVE |
| COLUMNS WITH BLOCK INFILL, IF SO PROVIDE THE EQUIVALENT |
| THICKNESS OF WALL AND FIRE RATING PER 721.2.1.1. |
| B) THE PROPERTY APPRAISERS WEB SITE SHOWS THE ASHLEY |
| FURNATURE STORE ON SEPERATE PROPERTY, THIS REQUIRES A 3 |
| HR RATED FROM BOTH PROPERTIES NOT A 4 HR RATED FIRE |
| WALL. A UNITY OF TITLE BETWEEN THE LOTS WOULD THEN MAKE |
| THE 4 HR FIRE WALL FOR TWO INDEPENDANT BUILDINGS ON THE |
| SAME LOT. TABLE 603 BUILDING TYPE IIIA & IIIB/ |
| MERCANTILE OCCUPANCY. |
| C) PLEASE PROVIDE DETAIL OF HOW THE TWO FIRE RATED |
| WALLS WILL BE FIRE CAULKED OR SEALED BETWEEN THE TWO |
| WALLS. |
| D) PLEASE PROVIDE ADDITIONAL INFORMATION PER SECTION |
| FBC-B 706.5 HORIZONTAL CONTININUITY. |
| |
| 5) SHEET A2.2 DOOR OPENING # 8 PROVIDE WALL DETAIL FOR |
| FIRE RATED WALL, AGAIN THE RATED FIRE WALL STOPS SHORT |
| OF THE OPENING PROTECTIVES, PROVIDE A DETAIL OF THIS |
| AREA, TABLE 602. |
| |
| 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 7) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 8) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS/ MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS, INSULATIONS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |