Plan Review Notes
Plan Review Notes For Permit 12060319
Permit Number 12060319
Review Stop M
Sequence Number 1
Notes
Date Text
2012-07-09 16:43:37RESIDENTIAL (R3) REPAIRS MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- RETURN AIR TRANSFER DUCT SHOWN FOR THE MASTER
 BEDROOM DOESN'T COMPLY WITH SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL:
 A) TRANSFER DUCT SIZE NEEDS TO BE 1-1/2 TIMES THE CROSS
 SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE BEDROOM
 AND THE CLOSET.
  
 B) THE TRANSFER DUCT NEEDS TO BE LOCATED ON THE FAMILY
 AREA. THERE IS A DOOR IN THE MASTER BEDROOM VESTIBULE.
  
 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE PLANS. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  