Plan Review Notes For Permit 12060319 |
Permit Number |
12060319 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-07-09 16:43:37 | RESIDENTIAL (R3) REPAIRS MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC | | | | 1- RETURN AIR TRANSFER DUCT SHOWN FOR THE MASTER | | BEDROOM DOESN'T COMPLY WITH SEC. M1602.4 OF 2010 | | FBC-RESIDENTIAL: | | A) TRANSFER DUCT SIZE NEEDS TO BE 1-1/2 TIMES THE CROSS | | SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE BEDROOM | | AND THE CLOSET. | | | | B) THE TRANSFER DUCT NEEDS TO BE LOCATED ON THE FAMILY | | AREA. THERE IS A DOOR IN THE MASTER BEDROOM VESTIBULE. | | | | 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. | | | | 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE PLANS. SEC. 107.2.1 CITY AMENDMENTS | | TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|