2012-07-06 11:18:59 | BUILDING PLAN REVIEW |
| PERMIT: 12060319 |
| ADD: 7887 OLMPIA DR |
| CONT: MCMAHOUN & ASSOCATES |
| TEL: (561)313-7832 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET A1 INDICATES THE PRESSURES BOTH POSITIVE AND |
| NEGATIVE FOR CPMPONENTS AND CLADDING. THE PRODUCT |
| APPROVALS SUBMITTED DO NOT MEET THE PRESSURES REQUIRED |
| BY THE DESIGN PROFESSIONAL. NOTE THIS SSTRUCTURE IS |
| REVIEWED BY THE 2010 FBC-R ONE AND TWO FAMILY |
| RESIDENTIAL CODE, TABLE 301.2(2) PROVIDES THE MINIMUM |
| PRESSURES THAT ARE REQUIRED BY CODE. THE DESIGNER OF |
| RECORD DOES INDICATE PRESSURES THAT ARE DOUBLE WHAT IS |
| REQUIRED BY CODE. |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3) PLANS ARE DEFICIENT IN PROVIDING OCMPLIANCE WITH |
| 2010 FBC-R R302.5, R302.5.1 & TABLE R 302.6. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |